Osram PD BASIC Manuel d'utilisateur Page 2

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 2
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 1
Page 2 of 2
OSRAM GmbH
Kunden Service Center
Customer-Service-Center (CSC)
Steinerne Furt 62
86167 Augsburg
Germany
Tel : +49 (0) 1803 677 - 200
(kostenpichtig / charges apply)
Fax.: +49 (0) 1803 677 - 202
www.osram.com
www.osram.de
40503006399492
4050300639949
IV 2009
DALI_LS-PD_BASIC_ma0904en_we1.01.indd
Installation (cont.)
F
G
I
H
E
100°
100°
2,5 m
3,5 m
3 m
Vcc LS 0V
NCPDNC
OSRAM
DALI LS/PD
BASIC
Vcc
(+)
(-)
0V
LS
PD
58,5 42
70,5
Conformity with the relevant EU directives is
conrmed by the CE symbol.
Appendix
Technical data
Operating voltage Nominal 10 V DC
(8 – 20 V DC)
Current consumption Max. 3 mA DC
Maximum total line
length
100 m
Line connection Screw terminals for single-wire
or ne-wire conductors with 0.3 –
1.5 mm²
Operating temperature 0 °C … +50 °C
Operating range Up to 400 lx measured at sensor
Detection area Conical, opening angle approx.
100°
Pollution severity 2 (dry, not conductive, as per
IEC 664)
Dimensions
(L x W x H)
58.5 x 70.5 x 42 mm
Weight Approx. 70 g
Protection type IP 20
Protection class II
Selecting the installation location
E Optimal mounting height: 2.5 – 3 m. As the mounting height
increases, the detection area increases and sensitivity is
reduced.
F Monitoring cone: entire workplace; not on window surfaces
G Avoid exposure to direct light.
H Place devices that radiate heat outside of the monitoring
cone.
I Avoid drafts (e.g. from ventilators).
Dimensioned drawing
Connecting the sensor
K Light measurement value
L Motion signal
Vue de la page 1
1 2

Commentaires sur ces manuels

Pas de commentaire